GD10P – Gas detector
Tecnologia | Infrared |
---|---|
Measured gas | Acetaldehyde – C2H4O, Acetic acid – C2H4O2, Acetone / Propionaldehyde – C3H6O, Acetylene – C2H2, Benzene – C6H6, Butane – C4H10, Carbon Dioxide – CO2, Carbon disulfide – CS2, Carbonyl sulfide – COS, Chloroform – CHCl3, Cycloheptatriene – C7H8, Dichloromethane – CH2CL2, Dimethylbutane – C6H14, Ethane – C2H6, Ethanol – C2H6O, Ethylene – C2H4, Fluoromethane – CH3F, Hexane – C6H14, IC4 – IC4, IC5 – IC5, Isobutanol – C4H10O, Methane – CH4, Methanol – CH3OH, Methanol – CH4O, Methyl iodide – CH3I, Octane – C8H18, Pentane – C5H12, Phosgene – CCl2O, Propane – C3H8, Propanol – C3H7OH, Propylene – C3H6, Styrene – C8H8, Tetrachloroethylene – C2Cl4, Tetrafluoroethylene – C2F4, Tetrafluoromethane – CF4, Total HydroCarbons – THC, Trichloroethylene – C2HCl3, Xylene – C8H10 |
Manufacturer | Simtronics |
- Description
Description
Our ultimate Infra-Red point detector with versions covering a wide range of combustible gases.
Features
Life-time stability
The SimSource infrared light source is a solid-state component with a stable output and 60 years of expected lifteime. This, together with the Simtronics IR-path design gives you a detector with unparallelled stability.
No false alarms
Unlike most gas detectors in use today, the GD10P will give an error signal and not cause gas alarms in case of detector failure.
No poisioning or saturation
- Immune to silicon vapours, H2S and other widely used agents.
- High gas concentrations will not saturate the detector.
- Can be used to detect gases where oxygen is not present, e.g. in sub-sea production units
Specification
General | |
---|---|
Detection method | IR-absorbtion, dual wavelength, dual path |
IR-Source | Solid state IR source, 50Hz flash |
Gases detected | Hydrocarbons, see separate data sheet for CO2 detection |
Self-test | Continuous |
Calibration | Factory set, no field recalibration |
Performance | |
Lifetime stability | ±5% of full scale (FS) reading |
Accuracy | ±3% FS between 0-50 % reading |
±5% FS between 50-100 % reading | |
Response time | T20 = 1 sec. (Option 0.3 sec) |
T50 = 2.5 sec. (Option 0.7 sec) | |
T90 = 6 sec. (Option 1.6 sec) | |
Start-up time | Less than 60 sec. |
Output Signal | |
Standard | Current source 4 – 20 mA, max. load impedance 500 Ohm |
Option | Current sink 4 – 20 mA |
Option | HART® |
Detector warnings: | |
Early clean optics | Pre warning (1 mA pulse) |
Clean optics | Dirt accumulation (1 mA) |
Clean optics | Dirt accumulation (1 mA) |
Option: Dirt accumulation (2mA) | |
Detector failure | Internal fault (0 mA) |
Electrial | |
Power supply | 24 V DC, range18-32 V DC |
Power consumption | Approx. 3.5 W |
Connection | 3 wires (0.5mm2 – 1.5mm2) |
Cable entry | M20 EExe cable gland |
Temperature Range | |
Storage | -40°C to + 70°C (-40°F to +158°F) |
Operating | -40°C to + 65°C (-40°F to +149°F) |
Humidity (operation) | 100% RH |
Exsplosion Proof Housing | |
Main housing | EExd IIC T6 |
Terminal compartment | EExe |
Protection category | IP66/IP67 DIN 40050 |
Housing material | Stainless steel SIS2343 (ASTM 316) |